M25 Grade Concrete Mix Design – IS10262 Recent Revision

Learn Mix design of M25 Grade Concrete as per Indian standard codebooks – IS10262 -CONCRETE MIX PROPORTIONING – GUIDELINES and IS456.

I. STIPULATIONS FOR PROPORTIONING

This section contains the conditions or requirements specified or expected from the concrete. you can adjust the values in the section to suit your needs

Please view on Landscape mode to get better view on a mobile phone.

AGrade DesignationM25
BType of CementOPC 53
CMaximum Nominal
Size of Aggregate
20mm
DMinimum Cement Content300kg Table 5-IS456
EMaximum Cement Content450kg As per clause
8.2.4.2
FMaximum W/C ratio0.50Table 5-IS456
GWorkability75mmFor RCC
As per code
Table 5 Minimum Cement Content, Maximum Water-Cement Ratio for M25 grade concrete  IS456 codebook
Table 5 Minimum Cement Content, Maximum Water-Cement Ratio for Mix design of M25 grade concrete – IS456 codebook

II. TEST DATA FOR MATERIALS

The values ​​in this section should be based on laboratory tests on materials according to the relevant code book. The values ​​given here are the standard values ​​of everyday construction materials used in India.

ACement UsedOPC 53Confirming to
IS8112
BSpecific Gravity of Cement3.15Test – IS: 2720 
CSpecific Gravity ofTest – IS 2386
Coarse Aggregate2.74
Fine Aggregate2.74
DWater Absorption Test – IS 2386
Coarse aggregate 0.5 %
Fine aggregate  1 %
ESieve Analysis Test – IS 2386
Coarse aggregate Confirming to
Table 2-IS383
Fine aggregate  Zone II Confirming to
Table 4-IS383

III. TARGET STRENGTH

The mixing method, climate, curing and other factors can affect the strength of the concrete, so it is important to design the concrete with greater strength than the actual requirement.

Target strength (Fck) must be greater than the Designated Characteristic strength (fck). The target strength for m20 grade concrete can be found from the formula given in the code book.

Fck = = fck.+1.65s

Standard deviation (S) value for the M25 grade concrete is given in table 1 of IS10262.

Standard Deviation for M25 grade Concrete - IS10262 Codebook
Table 1 Standard Deviation for M25 grade Concrete – IS10262 Codebook
Fck= fck.+1.65s “S” from Table1-IS10262
Fck= 25+(1.65 x 4)S = 4
Fck= 31.6 N/mm2

The target strength required for our concrete is 31.6 N / mm2. That is, after curing in water for 28 days, the compressive strength of the concrete should be at least 31.6 N / mm2 when tested on a direct compression test machine (CTM).

IV. SELECTION OF WATER-CEMENT RATIO

The maximum water-cement ratio for M25 grade concrete can be found in Table 5-IS456 given above.

Maximum W/C ratio=0.50Table 5-IS456
Adopted W/C ratio=0.50

You can reduce the water-cement ratio for M25 grade concrete based on your requirements, but remember that the Water-cement ratio directly affects the strength of the concrete.

V. SELECTION OF WATER CONTENT

Maximum water content to get slump up to 50mm when using a 20mm aggregate is used is given in Table 2 of IS10262.

Table 2 Maximum Water Content per cubic meter - IS10262
Table 2 Maximum Water Content per cubic meter – IS10262

If we use 20mm aggregate we need the following water content to get a 50mm slump in concrete

Maximum Water Content = 186 L

However, according to the specification given in Section 1, our concrete requires a slump of 75 mm. Clause 4.2 of IS Code suggest an increase of 3% in water content would result in increase in slump of 25 mm from the actual 50 mm slope.

Therefore, to obtain a slump of 75 mm over a total of 20 mm:-

Water-content for 75mm Slump= 186+(0.03*186)As per Clause 4.2
= 191.58 L
Adopted Water Content= 190 L

VI. CALCULATION OF CEMENT

The weight of cement required for M25 grade concrete can be calculated from the water-cement ratio and the water content.

Adopted Water Cement Ratio= 0.50
Cement required= Water Content / W-C Ratio
= 190/0.5
= 380 kg
Adopted Cement Content= 380 kg

VII COARSE AND FINE AGGREGATE

The coarse aggregate ratios for different zones of fine aggregates are given in Table 3 of IS10262.

Table 3 Volume of coarse aggregate to total aggregate for mix design of M25 grade concrete - IS10262
Table 3 Volume of coarse aggregate to total aggregate ratio for Mix Design of M25 concrete – IS10262

As per specification, for Maximum Nominal size of aggregate = 20mm & Fine aggregate = Zone II:-

Coarse Aggregate ratio=0.62 Table3-IS10262
Final Fine Aggregate ratio= 0.38(1-0.62) = 0.38

VIII MIX CALCULATIONS OF M25 GRADE CONCRETE

This section deals with calculation of fine aggregate and coarse aggregate from aggregate ratios, cement and water.

AVolume of Concrete= 1 cu.m
BTotal Volume of Cement= Cement/(S.G*1000)
= 380/(3.15*1000)
= 0.121 cu.m
CVolume of Water= Water /(S.G*1000)
= 190/(1*1000)
= 0.190 cu.m
DTotal Aggregates requirement= A – (B+C+D+E)
= 1 -(0.121+0.190)
= 0.689 cu.m
ECoarse Aggregate (C.A)= F * C.A ratio * S.G * 1000
= 0.689*0.62*2.74 *1000
= 1171 kg
FFine Aggregate (F.A)= F * F.A ratio * S.G * 1000
= 0.689*0.38*2.74 *1000
= 717 kg

Cement Fine and Coarse Aggregate needed for M25 grade concrete

S.No.MATERIALSQUANTITY
1Cement380 kg
2Fine Aggregate 717 kg
3Coarse Aggregate (20mm)1170 kg
4WATER190 L

To find the design mix ratio, divide the calculated value of all materials by the weight of the cement. Therefore the Mix Design Ratio of M25 Grade concrete by weight is Cement: F.A: C.A: Water = 1: 1.9 :3.1 : 0.50

Note: This is a Design mix ratio by weight which is different from the Nominal volumetric mix ratio. Read this post to understand the difference between Nominal Mix and Design Mix.

Workability Requirements for Different Concrete as per IS456 Codebook
Standard Deviation for M25 grade Concrete - IS10262 Codebook
Table 1 Standard Deviation for M25 grade Concrete – IS10262 Codebook


Comments

Leave a Reply

Your email address will not be published. Required fields are marked *